Ammeter design
A meter designed to measure electrical
current is popularly called an "ammeter" because the unit of
measurement is "amps."
In ammeter designs, external resistors added
to extend the usable range of the movement are connected in
parallel with the movement rather than in series as
is the case for voltmeters. This is because we want to
divide the measured current, not the measured voltage, going
to the movement, and because current divider circuits are
always formed by parallel resistances.
Taking the same meter movement as the
voltmeter example, we can see that it would make a very
limited instrument by itself, full-scale deflection
occurring at only 1 mA:
As is the case with extending a meter
movement's voltage-measuring ability, we would have to
correspondingly re-label the movement's scale so that it
read differently for an extended current range. For example,
if we wanted to design an ammeter to have a full-scale range
of 5 amps using the same meter movement as before (having an
intrinsic full-scale range of only 1 mA), we would have to
re-label the movement's scale to read 0 A on the far left
and 5 A on the far right, rather than 0 mA to 1 mA as
before. Whatever extended range provided by the
parallel-connected resistors, we would have to represent
graphically on the meter movement face.
Using 5 amps as an extended range for our
sample movement, let's determine the amount of parallel
resistance necessary to "shunt," or bypass, the majority of
current so that only 1 mA will go through the movement with
a total current of 5 A:
From our given values of movement current,
movement resistance, and total circuit (measured) current,
we can determine the voltage across the meter movement
(Ohm's Law applied to the center column, E=IR):
Knowing that the circuit formed by the
movement and the shunt is of a parallel configuration, we
know that the voltage across the movement, shunt, and test
leads (total) must be the same:
We also know that the current through the
shunt must be the difference between the total current (5
amps) and the current through the movement (1 mA), because
branch currents add in a parallel configuration:
Then, using Ohm's Law (R=E/I) in the right
column, we can determine the necessary shunt resistance:
Of course, we could have calculated the same
value of just over 100 milli-ohms (100 mΩ) for the shunt by
calculating total resistance (R=E/I; 0.5 volts/5 amps = 100
mΩ exactly), then working the parallel resistance formula
backwards, but the arithmetic would have been more
challenging:
In real life, the shunt resistor of an
ammeter will usually be encased within the protective metal
housing of the meter unit, hidden from sight. Note the
construction of the ammeter in the following photograph:
This particular ammeter is an automotive
unit manufactured by Stewart-Warner. Although the D'Arsonval
meter movement itself probably has a full scale rating in
the range of milliamps, the meter as a whole has a range of
+/- 60 amps. The shunt resistor providing this high current
range is enclosed within the metal housing of the meter.
Note also with this particular meter that the needle centers
at zero amps and can indicate either a "positive" current or
a "negative" current. Connected to the battery charging
circuit of an automobile, this meter is able to indicate a
charging condition (electrons flowing from generator to
battery) or a discharging condition (electrons flowing from
battery to the rest of the car's loads).
As is the case with multiple-range
voltmeters, ammeters can be given more than one usable range
by incorporating several shunt resistors switched with a
multi-pole switch:
Notice that the range resistors are
connected through the switch so as to be in parallel with
the meter movement, rather than in series as it was in the
voltmeter design. The five-position switch makes contact
with only one resistor at a time, of course. Each resistor
is sized accordingly for a different full-scale range, based
on the particular rating of the meter movement (1 mA, 500
Ω).
With such a meter design, each resistor
value is determined by the same technique, using a known
total current, movement full-scale deflection rating, and
movement resistance. For an ammeter with ranges of 100 mA, 1
A, 10 A, and 100 A, the shunt resistances would be as such:
Notice that these shunt resistor values are
very low! 5.00005 mΩ is 5.00005 milli-ohms, or 0.00500005
ohms! To achieve these low resistances, ammeter shunt
resistors often have to be custom-made from relatively
large-diameter wire or solid pieces of metal.
One thing to be aware of when sizing ammeter
shunt resistors is the factor of power dissipation. Unlike
the voltmeter, an ammeter's range resistors have to carry
large amounts of current. If those shunt resistors are not
sized accordingly, they may overheat and suffer damage, or
at the very least lose accuracy due to overheating. For the
example meter above, the power dissipations at full-scale
indication are (the double-squiggly lines represent
"approximately equal to" in mathematics):
An 1/8 watt resistor would work just fine
for R4, a 1/2 watt resistor would suffice for R3
and a 5 watt for R2 (although resistors tend to
maintain their long-term accuracy better if not operated
near their rated power dissipation, so you might want to
over-rate resistors R2 and R3), but
precision 50 watt resistors are rare and expensive
components indeed. A custom resistor made from metal stock
or thick wire may have to be constructed for R1
to meet both the requirements of low resistance and high
power rating.
Sometimes, shunt resistors are used in
conjunction with voltmeters of high input resistance to
measure current. In these cases, the current through the
voltmeter movement is small enough to be considered
negligible, and the shunt resistance can be sized according
to how many volts or millivolts of drop will be produced per
amp of current:
If, for example, the shunt resistor in the
above circuit were sized at precisely 1 Ω, there would be 1
volt dropped across it for every amp of current through it.
The voltmeter indication could then be taken as a direct
indication of current through the shunt. For measuring very
small currents, higher values of shunt resistance could be
used to generate more voltage drop per given unit of
current, thus extending the usable range of the (volt)meter
down into lower amounts of current. The use of voltmeters in
conjunction with low-value shunt resistances for the
measurement of current is something commonly seen in
industrial applications.
The use of a shunt resistor along with a
voltmeter to measure current can be a useful trick for
simplifying the task of frequent current measurements in a
circuit. Normally, to measure current through a circuit with
an ammeter, the circuit would have to be broken
(interrupted) and the ammeter inserted between the separated
wire ends, like this:
If we have a circuit where current needs to
be measured often, or we would just like to make the process
of current measurement more convenient, a shunt resistor
could be placed between those points and left their
permanently, current readings taken with a voltmeter as
needed without interrupting continuity in the circuit:
Of course, care must be taken in sizing the
shunt resistor low enough so that it doesn't adversely
affect the circuit's normal operation, but this is generally
not difficult to do. This technique might also be useful in
computer circuit analysis, where we might want to have the
computer display current through a circuit in terms of a
voltage (with SPICE, this would allow us to avoid the
idiosyncrasy of reading negative current values):
shunt resistor example circuit
v1 1 0
rshunt 1 2 1
rload 2 0 15k
.dc v1 12 12 1
.print dc v(1,2)
.end
v1 v(1,2)
1.200E+01 7.999E-04
We would interpret the voltage reading
across the shunt resistor (between circuit nodes 1 and 2 in
the SPICE simulation) directly as amps, with 7.999E-04 being
0.7999 mA, or 799.9 �A. Ideally, 12 volts applied directly
across 15 kΩ would give us exactly 0.8 mA, but the
resistance of the shunt lessens that current just a tiny bit
(as it would in real life). However, such a tiny error is
generally well within acceptable limits of accuracy for
either a simulation or a real circuit, and so shunt
resistors can be used in all but the most demanding
applications for accurate current measurement.
-
REVIEW:
-
Ammeter ranges are created by adding
parallel "shunt" resistors to the movement circuit,
providing a precise current division.
-
Shunt resistors may have high power
dissipations, so be careful when choosing parts for such
meters!
-
Shunt resistors can be used in conjunction
with high-resistance voltmeters as well as low-resistance
ammeter movements, producing accurate voltage drops for
given amounts of current. Shunt resistors should be
selected for as low a resistance value as possible to
minimize their impact upon the circuit under test.
|